Equipment Rentals • Sales • 24/7 Emergency Support Service • Serving all of British Columbia • 604-323-1222

Equipment Rentals

25 KW- DIESEL GENERATOR- WACKER NEUSON G25

Pricing Information

Request Quote

Product Description

  • Ideally suited for construction sites where durability, reliability and flexibility are required to supply continuous power for applications such as lighting, cranes, concrete mixers and conveyor belts.
  • Brushless, oversized alternators with separate excitation winding and AVR (Automatic Voltage Regulation) provide superior motor starting and enhanced ability to run non-linear loads.
  • Single switch start and simple, uncluttered control panel provide unmatched ease of use.
  • Automatic remote start capability standard which is ideal for temporary standby applications.
  • BC’s leading equipment rentals and sales resource
  • Industry’s most knowledgeable, experienced and helpful staff.
  • 24/7 Emergency Support Services
  • Mobile Equipment Operator Training

Got a question? We’re here to help. 604-323-1222

Search Inventory
View

Support Services

Additional Product Info & Specs

Operating data

Trailer coupling Type2in Ball
Standby output20.4 kW
Prime output19.5 kW
Voltage 3 Phase240/480 V
Current 3 Phase (Prime)58/29 A
Current 1 Phase (Prime)120/240 A
Voltage 3 Phase208, 220, 240, 416, 440, 480 V
Voltage 1 Phase120, 127, 139, 240, 254, 277 V
Circuit breaker (Main)70 A
Frequency60 Hz
Power factor 1 Phase1 cos Φ 1~
Power factor 3 Phase0.8 cos Φ 3~
Sound level (LwA) at Prime (23 ft / 7 m)65 dB(A)
Receptacles -20 Amp GFI Duplex2
Receptacles -50 Amp Twist Lock2

Engine / Motor

Engine / MotorLiquid-Cooled, 4 Cylinders
Engine / Motor manufacturerIsuzu
Emissions CertifiedTier 4i
Displacement133 in³
Operating performance SAE J1995, ISO 8528-135.4 hp
at rpm1,800 rpm
Coolant Capacity11.9 US qt
Engine oil Capacity8.5 US qt
Fuel typeDiesel
Fuel consumption (Prime Load)1.8 US gal/h
Tank capacity -Fuel58.4 US gal
Quantity (Battery)1
Battery12 V
Generator modelMecc Alte, Brushless w/AVR
Voltage control No Load to Full Load +/-1 %
Voltage control Steady State +/-0.2 %
Generator insulation (class)H
Frequency (Generator Speed)60 Hz
Runtime at 100% Prime Load32.2 h
Runtime at 75% Prime Load24.15 h
Product Specifications

Request A Quote